Manufactures of Fibreglass Roofing Products since 1983

Home Page

About Us

Fibreglass Products

Polycarbonate Products

Roof Ventilators

Plastic Lattice

Sump Jet roof drainage

Profiles

Installation details

Safety Data

New Products

Distributors

Contact Us

Architects, Specifiers &
Commercial Partners Login

 

 

Installation Details

Click here for Fixing details

 

SCOPE

The following section sets out requirements for the installation of plastic roof and wall cladding sheets in a roof or wall structure. All fixing done to AS 1562-3-2006.

 

ROOF AND WALL CLADDING SHEETS

General Provisions

Inspection
Prior to installation, the installer shall inspect the rafter and batten spacing in roofs, and the stud and noggin spacing in walls, to establish that their layout will provide the required laps and any specified overhangs, e.g. eaves.

Cutting of sheets
Cutting and cut edge finishing shall be carried out as recommended by the manufacturer/supplier or by other means to achieve a cut with minimal damage to the sheet.

Supports at hips and valleys
Hip and valley trimmers shall be provided and shall be fixed flush with the top face of purlins and spanning between them. They shall run parallel to the edge of the sheeting, and shall be placed so as to permit the fastening of the sheeting or of hip ridging.

End laps
A minimum of 200 mm overlap shall be provided at all ends (including those with dissimilar materials) and such lap shall be supported with a rafter, batten, stud, or noggin (dwang).

All sheets, when fastened, shall have full bearing on rafters, battens, studs or noggins (dwangs) and their ends shall extend not less that 50 mm beyond the point of fastening.

At all end laps between plastic and dissimilar material sheeting, two lines of compressive foam strip or of flexible sealant shall be placed across the full width of the lap approximately 150 mm apart with one line 25 mm from the end of the plastic sheeting.

NOTES:

  1. The compressive foam strip should be light in colour for PVC and preferably be of the type impregnated with a weather-resistant viscous fluid.
  2. Some sealants are not compatible with certain types of plastic materials and can lead to stress and cracking if incorrectly used. The manufacturer’s instructions should be followed carefully.

Side laps at inserts
Each individual plastic building sheet shall overlap and be supported by adjacent roof or wall cladding in accordance with eh manufacturer’s installation instructions.

At the overlapping joint between plastic sheeting and adjacent sheeting additional side-lap fasteners may be required in accordance with the manufacturer’s instructions. In these cases the fasteners shall bond the plastic sheeting and the adjacent sheeting together, and appropriate allowances shall be made for the differential expansion rates of the materials and with the provision of a suitable sealing washer at each fixing point.

Projections through sheeting
Where any projections such as pipes, ducts, chimneys and the like pass through sheeting, they shall be adequately insulated and flashed. For roofs, such projections shall pass through the pan of pan type sheets or through the crest of the corrugation or corrugated sheets. Where this is not possible because of the position or size of the projection, ribs or corrugations shall be cut away as required, provided that such cut ribs or corrugations are adequately flashed and that, where necessary, all cut sections of the sheeting are supported by additional roof framing. In such cases, all cutting and flashing shall be arranged so that adequate provision is made for drainage of all pans or corrugations.

Fastening procedure
Wherever possible, plastic sheeting shall be fastened concurrently with the other materials. Normal sheet installation shall be followed, and the sheets shall be installed using fasteners that are strong enough to securely fasten the sheet. All fasteners shall be provided with adequate sealing. All fasteners shall be tightened to provide a weatherproof seal without deformation or damage to the sheet profile. The number of fasteners shall be in accordance with the sheet manufacturer’s instructions.

Unless otherwise specified, side lap fasteners shall be provided at joins with other more rigid sheeting material in accordance with the sheet manufacturer’s instructions.

Fastener types
Nails and pop-rivets shall not be used to secure plastic roof and wall cladding sheets. The following types of fasteners may be used:

(a) Hook bolts and nuts.

(b) Cranked hook bolts and nuts.

(ac) Square-bend L-hook bolts and nuts.

(d) Square-bend U-bolts and nuts.

(e) Round-bend U-bolts and nuts.

(f) J-bolts and nuts.

(g) Self-tapping screws.

(h) Roofing bolts, nuts and clips.

(i) Cone-head roofing screws.

(j) Toggle fasteners.

(k) Compression fasteners.

(l) TEK fasteners.

NOTE:
Nails and pop-rivets may be used for uPVC wall cladding boards when used in accordance with the manufacturer’s instructions

Fastener holes
In roofing applications, holes shall be drilled through the crest of any profiles except where valley fasteners are specified for the installations. For walls, fastening may be through the crest or valley of the profile.

All holes for fasteners shall be pre-drilled in exact positions to suit supporting members, i.e., on the centre-line of timber or metal supports, or, if normal hook bolts are used, as close as possible to the edge of the supports.

NOTE: It is usual for such holes to be drilled with the sheet in position. Stack drilling methods should not be used. Holes are drilled oversize to accommodate thermal expansion. The coefficient of linear expansion of plastic roof and wall cladding materials may be taken as follows:

(a) uPVC ……………………………………………………    7 x 10-5 per 1°C.

(b) GRP ……………………………………………………     2.5 x 10-5 per 1°C.

(ac) Polycarbonate ……………………………………     7 x 10-5 per 1°C.

Washers
All washers shall be of a type that will compress to provide a weatherproof seal over the fixing hole and of a type that will support the sheeting during actual wind load conditions.

NOTE: Some washers are not compatible with certain types of plastic materials and can lead to stress cracking if incorrectly used. The manufacturer’s instructions should be adhered to.

Sealing at flashings on roofs
Plastic roof sheeting is not easily reshaped after manufacture and will require special weather seals to be provided at all flashing and capping points. Typically a foam closure strip matching the profile of the plastic sheeting should be provided to seal the corrugations or pans of the profile under each flashing. The foam closure should be bonded to the pans or valleys of the plastic sheeting with a flexible waterproof sealant and should be continuous over the entire width of the plastic sheeting. Ideally it should be fitted at least 100 mm behind the turn down of the flashing.
NOTE: Some sealants are not compatible with certain types of plastic materials and can lead to stress cracking if incorrectly used. The manufacturer’s instructions should be adhered to.

Unsupported overhang
The maximum unsupported overhang allowable for GRP, PVC and polycarbonate shall be in accordance with the provision of the following Table:

TABLE OF MAXIMUM ALLOWABLE OVERHANG

Sheet type Maximum unsupported overhang
GRP 150 mm
PVC 50 mm
Polycarbonate
50 mm

 

Installation of safety mesh

Where wire safety mesh is incorporated under plastic roofing sheeting and where the safety mesh passes over the supporting member (purlin, batten or the like) directly under the plastic sheeting, a compressive foam strip of minimum 6mm thickness or solid strip of minimum 1 mm thickness shall be provided between the plastic sheeting and the safety mesh. The protective strip of material shall be the full width of the face of the supporting member and extend at least 25 mm past both edges of the plastic roof sheeting (or safety mesh).
NOTE: The compressive foam strip should be light in colour for PVC and preferably be of the type impregnated with a weather-resistant viscous fluid.

When plastic roof sheeting is supported at both edges of each sheet by the adjacent roofing, safety mesh shall be the full width of the opening between the two adjacent roof sheets. Where the plastic sheeting is not supported at the edges, the safety mesh shall extend a minimum of 600mm past the unsupported edge of the plastic sheet.

Fixing Details

FGW Fibrelite sheeting shall be installed in accordance with Australian Standards 1562.3, 2006 design and installation of sheet roof and wall cladding Part 3: Plastic combined with FGW fixing instructions.

Fixing of fibreglass GRP for roof applications; each ridge to be fastened at both ends and every second ridge at intermediate purlins. Predrill clearance holes 3-4mm above fixing screw diameter to allow for thermal expansion.

Sheeting shall be installed using the correct recommended fastening screws to suit the cladding together with a 32mm weather washer to avoid water penetration. The fixing screws should not be over tightened to the extent that the sheeting could buckle.

Lapping of sheets should be a minimum of 300mm and sealed with 2 continuous beads of suitable non setting sealant across the full width of the sheet.

Safety mesh should be used under fibreglass roofing in conjunction with purlin tape (75mm x 5mm) or a 65mm wide fibreglass protection strip should be installed over the safety mesh to avoid fracturing of the underside of the sheeting.

Span Chart

                  Sheet Weight g/M2

Recommended Number
of Main Fasteners
  2400 3050 3660 4880 Roof Wall
Profile Maximum allowable span Mid
Span
End
Span
Mid
Span
End
Span
Custom Orb 1200 1500 1600   4 6 6 6
Trimdek 1500 1700 2000   5 5 5 5
Spandek 1700 2100 2400 2800 5 5 5 5
QuickRib 900 1500 1600 2000   4 4 4 4
Kliplok 406 1400 1700 2000 2700 3 3 3 3
    
Copyright © 2009 -2011 FGW Corporation Pty Ltd, 14 Reihill Road, Maddington, WA 6109